| Inverter L300P |
400 V - Series |
| 015 HFE2 |
022 HFE2 |
040 HFE2 |
055 HFE2 |
075 HFE2 |
110 HFE2 |
150 HFE2 |
185 HFE2 |
220 HFE2 |
300 HFE2 |
370 HFE2 |
450 HFE2 |
550 HFE2 |
750 HFE2 |
900 HFE2 |
1100 HFE2 |
1320 HFE2 |
| Applicable motor (kW) |
1.5 |
2.2 |
4.0 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
75 |
90 |
110 |
132 |
Rated
output Current (a) |
3.8 |
5.3 |
8.6 |
12 |
16 |
22 |
29 |
37 |
43 |
57 |
70 |
85 |
105 |
135 |
160 |
195 |
230 |
| Rated input voltage |
3 ~ 380 ...480 V, ±10%, 50/60 Hz |
| Rated ouput voltage |
3 ~ 380 ...480 V (Corresponding to input voltage) |
Filter reference FPFB or
BTFB |
013 |
032 |
064 |
080 |
115 |
150 |
220 |
260 |
| Output frequency range |
0.1 ...400Hz |
| Frequency accuracy (at 25°C ± 10°C) |
Analogue setting: ±0.2%,digital setting: ±0.01% |
| Frequency resolution |
Analogue setting: Maximum frequency/400, digital setting: 0.01 Hz |
| V/f charact-eristics |
V/f (constant torque, reduced torque, optionally variable) |
| Overload capacity |
120% for 60s, 150% for 0.5s |
| Accele- ration/ decele- ration time |
0.01 - 3600 sec. (Linear/curve,accel./decel. Selection),Two stage accel./decel. |
| Banking |
|
| Dynamic Braking |
Built-in Brd circuit up to 15kW |
external dynamic braking unit (option) |
| Minimum value of resistor in ohms |
100 |
100 |
70 |
70 |
50 |
50 |
50 |
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
| DC braking |
braking force,time and operation frequency |
| Inputs |
|
| Intelligent input terminals |
6 inputs, NO, or NC,PNP or NPC logic |
| Analogue inputs |
3 inputs, 0...10V,0/4...20 mA, -10...+10V |
| Outputs |
|
| Analogue outputs |
Analogue voltage 0 - 10 V & Analogue current |
Relay
outouts |
2 Relays Single Contact, 1 Relay Changeover Contact |
| PID loop operation |
air velocity, temperature etc. |
| Thermal motor protection |
Thermistor input PTC or NTC |
| Serial port |
RS485, RS422 |
| Remote control up and down |
Integrated Motorised potentiometer with/without setpoint storage |
| Bus Systems (optional) |
Profibus, LonWorks,DeviceNet |
| Standards |
CE, UL ,cUL, c-Tick |
| Protection |
Overcurrent,overvoltage,undervoltage,overload,Extreme high temprature,
ground fault protection at startup, electronic thermal overload protection etc.
|
| Environ- mental conditions |
|
Temp- erature/
humidity |
-10...+40 °C temperature,25...90% humidity (non condensing) |
| Vibration / installation |
| 5.9m/s |
2 |
L300p-015...300HFE, 2.94m/s |
2 |
L300P-370...1320HFE, 10...55Hz, altitude 1000 m |
| or less indoors, no corrosive gases or dust |
|
| Standards |
EN 50082-1 and - 2, EN50081 - 1 and 2 (with filter), EN50178 |
| Options |
Remote operation unit,Profibus, Devicenet, LonWorks
EMI filter, AC reactor,DC reactor |
| Protection class |
IP20 (NEMA 1) / (IP54 optoonal) |
IP20 (IP54 optional) |
IP00 (IP54 optional) |
| Weight kg (approx) |
3.5 |
5 |
12 |
20 |
30 |
60 |
80 |