| Inverter SJ300 |
400 V - Series |
| 007 HFE |
015 HFE |
022 HFE |
040 HFE |
055 HFE |
075 HFE |
110 HFE |
150 HFE |
185 HFE |
220 HFE |
300 HFE |
370 HFE |
450 HFE |
550 HFE |
750 HFE |
900 HFE |
1100 HFE |
1320 HFE |
| Applicable motor (kW) |
0.75 |
1.5 |
2.2 |
4.0 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
75 |
90 |
110 |
132 |
Rated output
Current (a) |
2.5 |
3.8 |
5.3 |
8.6 |
12 |
16 |
23 |
32 |
38 |
48 |
58 |
75 |
90 |
110 |
149 |
176 |
217 |
260 |
| Rated input voltage |
3 ~ 380 ...480 V, ±10%, 50/60 Hz |
| Rated ouput voltage |
3 ~ 380 ...480 V (Corresponding to input voltage) |
Filter reference
FPFB or BTFB |
013 |
032 |
064 |
080 |
115 |
125 |
220 |
260 |
Output frequency
range |
0.1 ...400Hz |
Frequency accuracy
(at 25 °C ± 10°C ) |
Analogue setting: ±0.2%,digital setting: ±0.01% |
| Frequency resolution |
Analogue setting: Maximum frequency/400, digital setting: 0.01 Hz |
| V/f characteristics |
V/f (constant torque, reduced torque, optionally variable),sensorless vector control,closed loop vector |
| Overload capacity |
150% for 60s, 200% for 0.5s |
| Acceleration / deceleration time |
0.01 - 3600 sec. (Linear/curve,accel./decel. Selection),Two stage accel./decel. |
| Starting torque |
200 % at 0.5 Hz (SLV mode) |
180 % at 0.5 Hz (SLV mode) |
| Revolution accuracy |
±0.5 % at vector control (option) from 5.0...50 Hz |
| Banking |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Dynamic Braking |
Built-in Brd circuit |
external dynamic braking unit (option) |
Minimum value of
resistor in ohms |
100 |
100 |
100 |
70 |
70 |
50 |
50 |
|
- |
- |
- |
- |
- |
- |
- |
- |
- |
- |
| DC braking |
braking force,time and operation frequency |
| Inputs |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Intelligent input terminals |
9 inputs, 8 intelligent, NO, or NC,PNP or NPN logic |
| Analogue inputs |
3 inputs, 0...10V,0/4...20 mA, -10...+10V |
| Outputs |
|
| Digital outputs |
5 outputs, Type "Open Collector",NO or NC, PNP or NPN logic |
| Analogue outputs |
3 Outputs, 0...10 V, 4...20mA, 1 PWM 0...10 V |
| Relay outouts |
Single Changeover Contact |
| PID loop operation |
air velocity, temperature etc. |
| Thermal motor protection |
Thermistor input PTC or NTC |
| Serial port |
RS485, RS422 |
Remote control up
and down |
Integrated Motorised potentiometer with/without setpoint storage |
Bus Systems
(optional) |
Optional Profibus, LonWorks,DeviceNet |
| Standards |
CE, UL ,cUL, c-Tick |
| Protection |
Overcurrent,overvoltage,undervoltage,overload,Extreme high temprature,
ground fault protection at startup, electronic thermal overload protection etc.
|
| Environmental conditions |
|
Temperature /
humidity |
10...+40 °C temperature,25...90% humidity (non condensing) |
Vibration /
installation |
| 5.9m/s |
2 |
SJ300-007...220HFE, 2.94m/s |
2 |
SJ300-300...1320HFE, 10...55Hz, altitude 1000 m |
| or less indoors, no corrosive gases or dust |
|
| CE |
EN 50082-1 and - 2, EN50081 - 1 and 2 (with filter), EN50178 |
| Options |
Remote operation unit,Profibus, Devicenet, LonWorks,Encoder Feedback
EMI filter, AC reactor,DC reactor |
| Protection class |
IP20 (IP54 optoonal) |
IP00 (IP54 optional) |
| Weight kg (approx) |
3.5 |
5.0 |
12 |
20 |
30 |
50 |
60 |
80 |